Industrial Protocol Integration (Modbus / OPC-UA / BACnet)
Three protocol-bridge extensions for industrial devices — Modbus, OPC-UA, BACnet — sharing one pattern: connect → collect → register as device → feed dashboards.
1. Solution Overview
Industrial devices speak many protocols; NeoMind uses three independent bridge extensions, each turning its protocol's points into NeoMind device metrics and hiding protocol differences.
| Protocol | Extension | Typical devices | Discovery | Data model |
|---|---|---|---|---|
| Modbus | modbus-bridge | PLCs, power meters, temp/humidity sensors, VFDs | Manual (IP/serial + register map) | Registers (Holding/Input/Coils/Discrete) |
| OPC-UA | opcua-bridge | SCADA, MES, industrial gateways, OPC-UA servers | Browse address space; nodes auto-register | Nodes (NodeID, any type) |
| BACnet | bacnet-bridge | HVAC, fire, access, building controllers | Who-Is/I-Am broadcast | Objects (analog/binary/multi-state) |
Data Flow (identical across all three):
2. Bill of Materials (BOM)
| Item | Spec | Purpose | Required |
|---|---|---|---|
| NeoMind platform | v0.9.0+ | Extension host | ✅ |
| Protocol bridge | modbus-bridge / opcua-bridge / bacnet-bridge (per device) | Protocol access | ✅ |
| Industrial devices | Modbus / OPC-UA / BACnet-capable PLCs, meters, servers, controllers | Data source | ✅ |
| Network reachable | NeoMind and devices on the same segment or routable | Communication | ✅ |
Additional network requirements: Modbus RTU devices connect through a serial port on the host running NeoMind; BACnet/IP discovery relies on UDP 47808 broadcast (see 7.1).
3. Install the Extensions
All three bridges are published on the official extension marketplace; the current version is 2.7.x (this guide uses 2.7.7). Install one or more as needed — they are independent of each other.
3.1 Install from the Marketplace (Recommended)
- Open the Extensions tab in the left navigation.
- Click the Extension Marketplace button (globe icon) in the toolbar.
- Search for the extension name —
modbus-bridge,opcua-bridge, orbacnet-bridge. - Click Install on the matching entry; NeoMind automatically picks the
.neppackage matching your platform / ABI, downloads, and installs it. - After installation the extension appears in the extension list and starts automatically.
3.2 CLI Install (Optional)
neomind extension market-list # Browse marketplace extensions
neomind extension market-install modbus-bridge # Install from marketplace (latest by default)
neomind extension market-install opcua-bridge --version 2.7.7
neomind extension market-install bacnet-bridge
3.3 Verify the Installation
- The extension card and the header of the extension detail page should show Running (green dot).
- Click the extension card to open the extension detail page and confirm the Overview / Config / Commands / Metrics / Logs tabs exist.
- Switch to the Metrics tab and confirm extension-level metrics are being reported (e.g.
connected_devices,total_poll_errors).
How to invoke commands: every operation of the three bridges (adding devices, browsing, read/write, subscribing) is an extension command. Two ways to invoke — fill in parameters on the Commands tab of the extension detail page; or call the REST API
POST /api/extensions/:id/commandwith body{"command":"...","args":{...}}. Theneomind extensionCLI has no command-invocation subcommand. The examples below work with both.
4. Which Protocol to Choose
| Your device | Choose |
|---|---|
| Power/water meter, temp/humidity, VFD, small PLC | Modbus (most common, lightest) |
| SCADA / MES / industrial gateway / device exposing an OPC-UA server | OPC-UA (secure, self-describing, browsable) |
| HVAC, fresh air, fire, access, building controller | BACnet (building-automation standard) |
If a device supports several, prefer OPC-UA (security + self-description + browsing).
5. Modbus (modbus-bridge)
The protocol and how the bridge works: Modbus is the most widely used master/slave protocol in industry — the master (NeoMind) reads and writes the device's raw 16-bit registers by slave address (slave_id): holding registers
holding(FC03 read / FC06, FC16 write), input registersinput(FC04), coilscoil(FC01 read / FC05, FC15 write), and discrete inputsdiscrete_input(FC02). Registers carry no unit and no decimal point; real-world quantities (voltage, temperature, energy) come from decoding viatype/scale/word_orderin the register map (see section 5.4).modbus-bridge works on a polling model: after
add_device, each device gets its own polling thread that reads every point in the register map at thepoll_interval_mscadence, decodes it, and writes it to that device's metrics; the connection is kept alive, with automatic reconnect and a growingpoll_errorscounter on failure. This is periodic master-side sampling — data freshness depends on the polling interval, devices never push on their own.
Supports Modbus TCP and RTU (serial), multi-device independent polling, and register decoding (int16 / uint32 / float32 etc.) with scaling. Added devices are automatically registered as NeoMind devices (type modbus_device), and register values are continuously written as device metrics.
5.1 Extension-Level Configuration
View / edit on the Config tab of the extension detail page:
| Parameter | Type | Default | Range | Description |
|---|---|---|---|---|
defaultPollInterval | Integer | 5000 | 100–60000 | Default polling interval (ms) when not overridden per device |
defaultTimeout | Integer | 3000 | 100–30000 | Default connection timeout (ms) |
5.2 Add a Device + Register Map
- Open the modbus-bridge extension detail page → Commands tab → select
add_device. - Fill the
deviceparameter with the device configuration JSON (one command adds one device). Register addresses are 0-based: holding register 40001 in the PLC manual corresponds toaddress: 0:
{
"device_id": "power_meter_1",
"name": "Power Meter 1",
"mode": "tcp",
"ip": "192.168.1.50",
"port": 502,
"slave_id": 1,
"poll_interval_ms": 1000,
"timeout_ms": 3000,
"registers": [
{ "name": "voltage", "address": 0, "count": 2, "type": "float32", "register_type": "holding", "scale": 0.1, "unit": "V" },
{ "name": "energy", "address": 10, "count": 2, "type": "uint32", "register_type": "holding", "unit": "kWh" }
]
}
- On success the command returns:
{ "success": true, "device_id": "power_meter_1", "message": "Device added and polling started" }
The extension immediately starts the first polling cycle and registers the device with the platform (device type modbus_device). Running add_device again with the same device_id replaces the old configuration and restarts polling — no duplicate device is created.
4. RTU devices: set mode to "rtu", drop ip / port, and provide serial_port (e.g. /dev/ttyUSB0) and baud_rate (default 9600); slave_id and baud rate must match the device.
Device configuration fields (device JSON):
| Field | Type | Required | Default | Description |
|---|---|---|---|---|
device_id | string | ✅ | — | Device identifier; also used as the platform device ID |
name | string | optional | device_id | Display name |
mode | string | ✅ | — | tcp / rtu |
ip | string | required for TCP | — | Device IP address |
port | integer | optional | 502 | Modbus TCP port |
serial_port | string | required for RTU | — | Serial path (e.g. /dev/ttyUSB0) |
baud_rate | integer | optional | 9600 | RTU baud rate |
slave_id | integer | ✅ | — | Slave/unit ID (1–247) |
poll_interval_ms | integer | optional | 5000 | Polling interval (ms) |
timeout_ms | integer | optional | 3000 | Connection timeout (ms) |
registers | array | optional | — | Register map (table below) |
Register fields (each item of registers[]):
| Field | Type | Required | Default | Description |
|---|---|---|---|---|
name | string | ✅ | — | Register name; becomes the device metric name |
address | integer | ✅ | — | 0-based start address |
count | integer | optional | 1 | Number of registers to read; uint32 / int32 / float32 span 2 registers, so use 2 |
type | string | ✅ | — | Decode type: uint16 / int16 / uint32 / int32 / float32 / bool |
register_type | string | optional | holding | holding (FC03) / input (FC04) / coil (FC01) / discrete_input (FC02) |
scale | number | optional | 0 | Raw value × scale (0 = no scaling), e.g. raw 245 × 0.1 → 24.5 °C |
unit | string | optional | — | Unit |
word_order | string | optional | big | Word order for two-register types: big (hi word first, Modbus standard) / little (some PLCs) |
Protocol limits: a single read fetches at most 125 registers for
holding/inputand 2000 forcoil/discrete_input. Entries exceeding the limit are skipped and logged.
📷 TODO screenshot | add_device config · suggested path
…/neomind/industrial-protocols/01-modbus-add.png
5.3 Verification (End to End: From Adding to Metrics)
After adding power_meter_1 per 5.2, a complete verification timeline:
- After the first polling cycle (about 1 second with
poll_interval_ms: 1000): the Devices page showspower_meter_1(Modbus Device) carryingconnected/poll_errors/last_poll_msplus one metric per register (voltage,energy). - Run
get_device_data(arg{"device_id": "power_meter_1"}) to check the decoded values:
{
"success": true,
"device_id": "power_meter_1",
"connected": true,
"poll_errors": 0,
"last_poll_ms": 12,
"registers": [
{ "name": "voltage", "value": 220.15, "unit": "V", "raw": [17673, 38912] },
{ "name": "energy", "value": 100000.0, "unit": "kWh", "raw": [1, 34464] }
]
}
Where the values come from: for voltage the wire carried two words 0x4509 and 0x9800 → decoded as float32 = 2201.5 → × scale: 0.1 = 220.15 V; for energy the wire carried 0x0001 and 0x86A0 → joined as uint32 = 100000 (no scale set, no scaling) → 100000 kWh. The raw array holds the raw 16-bit register words (shown in decimal) — compare them word by word against the device's register manual when debugging decoding.
- Run
list_devicesto check device and polling health:
{
"success": true,
"count": 1,
"devices": [
{ "device_id": "power_meter_1", "name": "Power Meter 1", "mode": "tcp", "connected": true,
"register_count": 2, "poll_interval_ms": 1000, "poll_errors": 0, "last_poll_ms": 12 }
]
}
- Extension detail page Metrics tab:
connected_devices≥ 1 andtotal_poll_errorsno longer growing. - Metrics enter the platform with DataSourceIds like
device:power_meter_1:voltageanddevice:power_meter_1:energy, ready to bind to dashboards or rules.
5.4 Decoding: Register Words → Engineering Values
The wire only ever carries unsigned 16-bit words; type decides how 1–2 words are interpreted, word_order decides the join order for two-register types, and scale applies one multiplication after decoding:
-
Single-register types (
count: 1):uint16is used as-is;int16is interpreted as two's complement (e.g. wire value0xFF9C= 65436 → interpreted as −100; withscale: 0.1that is −10.0 °C, a cold-storage scenario);boolmaps any non-zero word to 1. -
Two-register types (
uint32/int32/float32,countmust be 2): the two words are joined into 32 bits and then interpreted. Take the voltage register from 5.3, words0x4509and0x9800:word_order: big(default, Modbus standard, hi word first):(0x4509 << 16) | 0x9800 = 0x45099800→ IEEE 754 float 2201.5 → ×scale 0.1→ 220.15 V;word_order: little(some PLCs put the lo word first):(0x9800 << 16) | 0x4509 = 0x98004509→ decodes to garbage like −1.66×10⁻²⁴.- The uint32
energyworks the same way:0x0001,0x86A0→ big join0x000186A0= 100000 kWh; if the device is actually little and you read it as big, you get0x86A00001≈ 2.55×10⁹ — an astronomically wrong number.
When readings look absurd (huge or tiny negative), suspect
word_orderandcountfirst. -
scale:
decoded value × scale;scale: 0(default) means no scaling. Common conversions: temperature raw 245 × 0.1 → 24.5 °C; voltage raw 2301 × 0.001 → 2.301 V. The multiplication happens after type decoding — float32 values can be scaled too.
5.5 Read / Write Control
- Read:
read_registers(device_id, address, count)(on-demand read;register_typeacceptsholding(default) /input, max 125 registers per call). - Write:
write_register(device_id, address, value),write_registers(...values[]),write_coil(device_id, address, value),write_coils(...values[])— e.g. remote breaker close or setpoint changes. - Operations:
update_pollingto change the poll interval,set_register_mapto update the register map (polling restarts after replacement),remove_deviceto remove a device and unregister it from the platform.
Read holding registers — call arguments:
{ "device_id": "power_meter_1", "address": 0, "count": 2 }
Return:
{ "success": true, "device_id": "power_meter_1", "address": 0, "register_type": "holding", "count": 2, "data": [17673, 38912] }
data is raw wordsThe data returned by read_registers consists of raw 16-bit words with no type decoding or scaling (decoding only happens in the polling cycle). For engineering values use the value from get_device_data or the device metrics; keep data for cross-checking against the register manual.
Write a single holding register — call arguments:
{ "device_id": "power_meter_1", "address": 100, "value": 250 }
Return:
{ "success": true, "device_id": "power_meter_1", "address": 100, "value": 250, "message": "Register written successfully" }
Write limits: write_register value must be 0–65535; write_registers accepts at most 123 values per call; write_coil value takes the strings "true" / "false"; write_coils takes a boolean array, at most 1968 per call.
Fill in parameters on the Commands tab, or call the REST API to write a single holding register:
curl -X POST -H "X-API-Key: $NEOMIND_API_KEY" \
-H "Content-Type: application/json" \
-d '{"command":"write_register","args":{"device_id":"power_meter_1","address":100,"value":250}}' \
http://localhost:9375/api/extensions/modbus-bridge/command
6. OPC-UA (opcua-bridge)
The protocol and how the bridge works: OPC-UA is the information-interchange standard of industrial automation; its biggest difference from Modbus is that it is self-describing — the server organizes data into an address-space tree where every node has a NodeID, browse name, and data type, so clients can discover points by browsing like a filesystem instead of transcribing register maps by hand; and it adds signing / encryption plus username/password authentication at the transport layer.
opcua-bridge works on a subscription model:
connectestablishes a session →browsewalks the address space (browsed nodes enter the local cache and auto-register as NeoMind devices) →subscribecreates data-change subscriptions for the nodes you care about. Once subscribed, any change in a node value (sampled atinterval_ms) is landed on that node device's metrics — no need to poll every point, and no chat/notification-center messages are produced; updates appear as metrics on the Devices page and dashboards.
Connect to any OPC-UA server (opc.tcp://) with security mode none / sign / sign_and_encrypt and optional username/password, with automatic reconnect. Browsed nodes auto-register as NeoMind devices (type opcua_node) and continuously publish metrics — no per-point configuration needed.
6.1 Extension-Level Configuration
| Parameter | Type | Default | Range | Description |
|---|---|---|---|---|
sessionTimeout | Integer | 30000 | 1000–300000 | OPC-UA session timeout (ms) |
autoReconnect | String | "true" | true / false | Reconnect automatically on connection loss |
6.2 Connect (and Choosing a Security Mode)
- Open the opcua-bridge extension detail page → Commands tab → run
connect:
{ "server_url": "opc.tcp://192.168.1.60:4840", "security_mode": "sign_and_encrypt", "username": "op", "password": "***" }
After a successful connect, the server itself is registered as a device too (type opcua_server; ID is derived from the sanitized URL — : / . replaced with _, e.g. opcua-server-opc_tcp___192_168_1_60_4840) and carries the connection-level metrics; on disconnect it reconnects automatically per autoReconnect.
- How to pick the security mode (it must match the server-side policy exactly, otherwise the server rejects the session):
security_mode | Message protection | When to use | Prerequisites |
|---|---|---|---|
none (default) | Plaintext, unsigned | Isolated / controlled test segments, demos | None |
sign | Signed (tamper-proof), still plaintext | Trusted intranets needing integrity only | Client certificate trusted by the server |
sign_and_encrypt | Signed + encrypted | Production, cross-segment transport | Server-trusted client certificate + credentials |
Certificates and credentials follow the server's security policy: for
sign/sign_and_encryptrequest a client certificate from the OPC-UA server administrator and have it trusted;username/passwordare accounts created in the server's user management. Prefersign_and_encryptwhenever possible; only fall back tononewhen the server exclusively offers a None policy (a common vendor debug default — consider enabling a security policy on the server after evaluation).
6.3 Browse the Address Space and Auto-Registration
Run browse: node_id defaults to the root i=84 (the Objects folder is i=85 — recommended starting point for business points); max_depth defaults to 1 level, up to 10. The return JSON looks like:
{
"success": true,
"browse_from": "i=85",
"max_depth": 1,
"nodes": [
{ "node_id": "ns=2;s=Temperature", "browse_name": "Temperature", "display_name": "Temperature Sensor", "node_class": "Variable", "data_type": "Float" },
{ "node_id": "ns=2;s=Pressure", "browse_name": "Pressure", "display_name": "Pressure Sensor", "node_class": "Variable", "data_type": "Float" }
]
}
- Every node carries
node_id/browse_name/display_name/node_class(Object/Variableetc.); variable nodes also carrydata_type. - Browsed nodes are simultaneously placed into the local node cache (queryable via
list_nodes/get_node) and auto-registered as NeoMind devices — this is where "no per-point configuration" comes from. Naming rule:=,;,:and spaces in the node ID are replaced with_, prefixed withopcua-:
| Node NodeID | Generated device ID | Metric DataSourceId |
|---|---|---|
i=2258 | opcua-i_2258 | device:opcua-i_2258:value |
ns=2;s=Temperature | opcua-ns_2_s_Temperature | device:opcua-ns_2_s_Temperature:value |
Node IDs use standard OPC-UA notation: i=2258 (numeric) or ns=2;s=Temperature (namespaced string).
📷 TODO screenshot | browse address space · suggested path
…/neomind/industrial-protocols/02-opcua-browse.png
6.4 Subscribe to Data Changes
Run subscribe: node_ids accepts a JSON array or a comma-separated string; interval_ms defaults to 1000 (range 50–60000).
{ "node_ids": ["ns=2;s=Temperature", "ns=2;s=Pressure"], "interval_ms": 500 }
Return:
{ "success": true, "subscription_id": "sub-9f3c1a2e-…", "node_ids": ["ns=2;s=Temperature", "ns=2;s=Pressure"], "interval_ms": 500 }
Re-running subscribe for the same set of nodes does not create a duplicate — it returns "Subscription already exists for these nodes".
What a subscription push looks like — metric updates, not messages: when a node value changes, the bridge stores the new value together with quality (e.g. Good) and source_timestamp (server source timestamp) into the node cache, and once per metric cycle writes the three values to the node device (device_metrics_write):
{ "device_id": "opcua-ns_2_s_Temperature", "metric": "value", "value": 43.0, "timestamp": 1760000000000 }
In other words, what you see on the Devices page / dashboards is a new data point on the device:opcua-ns_2_s_Temperature:value metric; automation rules trigger on it as usual. No "OPC-UA message" ever reaches the notification center.
6.5 Verification
- Run
get_status:
{ "success": true, "connected": true, "nodes_count": 12, "subscriptions_count": 2, "total_commands": 9 }
- Extension detail page Metrics tab:
connected= 1,nodes_countgrows as you browse,subscriptions_countequals the number of active subscriptions. - The Devices page shows
opcua-<node-id>devices; each node device carries three metrics:value/quality/source_timestamp. - Metrics enter the platform with a DataSourceId like
device:opcua-ns_2_s_Temperature:value. - The
readcommand (argnode_ids) returns current node values so you can immediately verify collection.
6.6 Read / Write Control
Bulk-read current values — read(node_ids) returns:
{
"success": true,
"results": [
{ "node_id": "ns=2;s=Temperature", "value": 42.5, "quality": "Good" },
{ "node_id": "ns=2;s=Pressure", "value": 101.3, "quality": "Good" }
]
}
readreturns the latest value held in the node cache (updated by browse / subscribe) — prefer subscriptions to keep data fresh.
Write a node value: write(node_id, value, data_type) — value is a string; data_type is optional (e.g. Float, Int32) to specify the type explicitly.
write is a protective stubIn the current open-source build (2.7.x), write is a protective stub: the command returns an error and does not write to the server — preventing accidental writes to industrial servers from the bridge layer. For write control on OPC-UA points, use the device's own HMI / SCADA. Reads and subscriptions are unaffected.
- Unsubscribe / disconnect:
unsubscribe(node_ids)(node_idsformat same assubscribe),disconnect(clears the node cache and subscriptions). - Helper commands:
list_nodes/get_node(node_id)show cached node details (includingvalue/quality/source_timestamp);list_subscriptionslists all active subscriptions (subscription_id/node_ids/interval_ms/active).
REST example (read two nodes):
curl -X POST -H "X-API-Key: $NEOMIND_API_KEY" \
-H "Content-Type: application/json" \
-d '{"command":"read","args":{"node_ids":["i=2258","ns=2;s=Temperature"]}}' \
http://localhost:9375/api/extensions/opcua-bridge/command
7. BACnet (bacnet-bridge)
The protocol and how the bridge works: BACnet is the building-automation standard protocol (HVAC, fresh air, lighting, fire, access control). Its data model is objects: each device is identified by a device instance number (0–4194303) and carries a set of objects (e.g.
analog_input:1,binary_output:1), each with properties — the most used beingpresent_value(property 85). Control writes never touch the present value directly; they write into the object's internal 16-level priority array (lower number = higher priority, see 7.4).bacnet-bridge runs two kinds of background tasks on UDP 47808: one listener thread that receives I-Am responses and COV notifications, plus one polling thread per added device that periodically reads point present values. Polling is enough for slow-changing points; COV subscription is the choice for second-level responsiveness — the device pushes on every change, more real-time and lighter than polling.
BACnet/IP over UDP (default 47808) with Who-Is/I-Am discovery, property reads, control writes, and COV subscriptions. Discovered / added devices auto-register as NeoMind devices (type bacnet_device, ID bacnet_<device_id>).
7.1 Extension-Level Configuration
| Parameter | Type | Default | Range | Description |
|---|---|---|---|---|
bindAddress | String | 0.0.0.0 | — | Local IP to bind for BACnet/IP |
bindPort | Integer | 47808 | 1–65535 | UDP port for BACnet/IP |
defaultTimeoutMs | Integer | 3000 | 100–30000 | Default request timeout (ms) |
pollIntervalMs | Integer | 10000 | 1000–60000 | Default polling interval (ms) |
Deployment requirement: Who-Is/I-Am uses UDP broadcast. The network must allow sending/receiving UDP 47808 (including broadcast); broadcast does not cross routers, so NeoMind and the BACnet devices should be on the same Layer-2 network, or interconnected via a network that forwards broadcast.
7.2 Discover Devices + Add Polled Points
- Open the bacnet-bridge extension detail page → Commands tab → run
discover(optionallylow_id/high_idto bound the device-instance range, default 0–4194303;timeout_msdefaults to 3000 as the wait window). The extension sends a Who-Is broadcast to255.255.255.255:47808and collects I-Am responses during the window (up to 500 devices). The return JSON:
{
"success": true,
"count": 2,
"devices": [
{ "device_id": 100, "ip": "192.168.1.100", "port": 47808, "vendor_id": 5, "max_apdu": 1476 },
{ "device_id": 201, "ip": "192.168.1.101", "port": 47808, "vendor_id": 15, "max_apdu": 480 }
]
}
Field meanings: device_id is the BACnet device instance number (configured on the device, unique network-wide); vendor_id is the ASHRAE-assigned vendor number (numeric — useful for identifying the brand); max_apdu is the device's maximum APDU size. Note: discovery is not registration — discovered devices enter the internal device table (visible in list_devices, connected: true), but only devices added via add_device are registered into the NeoMind platform and produce metrics.
- Run
list_devicesto see discovered devices, andget_device/list_objectsto inspect a device's objects (analog / binary / multi-state input / output / value; each item carriesobject_type/instance/present_value/units/cov_subscribed). - Run
add_deviceto register a device manually and start polling selected points (deviceparameter):
{
"device_id": 100,
"ip": "192.168.1.100",
"port": 47808,
"name": "HVAC Controller",
"poll_interval_ms": 5000,
"objects": [
{ "object_type": "analog_input", "instance": 1, "name": "Temperature", "units": "degC" },
{ "object_type": "analog_input", "instance": 2, "name": "Humidity", "units": "%" },
{ "object_type": "binary_output", "instance": 1, "name": "Fan Status" }
]
}
It returns {"success": true, "device_id": 100, "ip": "192.168.1.100", "port": 47808, "message": "Device added and polling started"} — the device is registered into the platform as bacnet_100, and the polling thread reads each object's present_value into metrics every poll_interval_ms.
📷 TODO screenshot | Who-Is discovery · suggested path
…/neomind/industrial-protocols/03-bacnet-discover.png
7.3 Verification
- Run
get_statusfor a global view:
{
"success": true,
"status": {
"total_devices": 1, "connected_devices": 1,
"total_cov_subscriptions": 0, "active_cov_subscriptions": 0,
"listener_running": true, "bind_port": 47808
}
}
- Extension detail page Metrics tab:
connected_devices≥ 1; after COV subscriptions,cov_subscriptionsgrows. - The Devices page shows
bacnet_100(BACnet Device). Each polled object's present value becomes a device metric named<object_type>_<instance>(e.g.analog_input_1,binary_output_1), alongsideconnected/objects_count/last_seen. - Metrics enter the platform with a DataSourceId like
device:bacnet_100:analog_input_1. - The
list_objectscommand lets you confirm that present values refresh andcov_subscribedgets set.
7.4 Read Properties / Subscribe COV / Write Control
Prerequisite: the target device instance must already be in the internal device table (run
discoveroradd_devicefirst), otherwise the command fails withDevice not found: ….
Read a property — read_property call arguments (object_type defaults to analog_input; property_id defaults to 85; common values: 85 = present_value, 77 = object_name, 28 = description, 117 = units):
{ "device_id": 100, "object_type": "analog_input", "instance": 1, "property_id": 85 }
Return:
{ "success": true, "device_id": 100, "object_type": "analog_input", "instance": 1, "property_id": 85, "value": 23.5 }
The value type follows the property: present values are numeric (true / false for binary objects, a state number for multi-state), while text properties like object_name (77) return strings. If the device refuses the read you get BACnet error: class=…, code=…. To read several properties in one request use read_property_multiple (properties defaults to [85]):
{ "device_id": 100, "objects": [
{ "object_type": "analog_input", "instance": 1, "properties": [85, 77] },
{ "object_type": "analog_input", "instance": 2 }
] }
Return:
{ "success": true, "device_id": 100, "count": 3, "values": [
{ "object_type": "analog_input", "instance": 1, "property_id": 85, "value": 23.5 },
{ "object_type": "analog_input", "instance": 1, "property_id": 77, "value": "Room Temp" },
{ "object_type": "analog_input", "instance": 2, "property_id": 85, "value": 41.2 }
] }
Subscribe to COV — subscribe_cov(device_id, object_type, instance), lifetime defaults to 0 (indefinite, in seconds), confirmed defaults to true (device must acknowledge each notification):
{ "device_id": 100, "object_type": "analog_input", "instance": 1 }
Return:
{ "success": true, "subscriber_id": 1, "device_id": 100, "object_type": "analog_input", "instance": 1, "lifetime": 0, "confirmed": true, "message": "COV subscription active" }
What you receive after a COV subscription — again metric updates, not messages: when the point changes, the device pushes a COV notification (subscriber ID + object identifier + list of property values); the bridge's background listener parses it, updates the point's present_value in the internal object cache, and sets cov_subscribed = true; the value then flows to the platform as the device:bacnet_100:analog_input_1 metric — you see the present value refresh on the Devices page / dashboards and rules trigger as usual. list_objects shows the object's refreshed present_value and cov_subscribed: true, and get_status counts it in active_cov_subscriptions. To cancel, call unsubscribe_cov with the subscriber_id returned by subscribe_cov.
Write control — write_property(device_id, object_type, instance, value, priority). Only output / value objects are writable (analog_output, binary_value, etc.; inputs are read-only). Always pass value as a string; the bridge infers the type in order: "true" / "false" → boolean (use for binary objects); pure integer → unsigned integer; decimal → real; anything else → string. Integer writes to analog output / value are coerced to REAL per ASHRAE 135-2020.
priority and priority-array semantics: a write does not set present_value directly — it writes one level of the object's 16-level priority array (1 highest, 16 lowest), and present_value always equals the highest-priority non-empty level. Common level conventions:
| Level | Conventional use |
|---|---|
| 1 | Life safety (highest — do not use) |
| 8 | Manual operator / maintenance writes (used in this extension's examples) |
| 16 | Lowest (BACnet default level — scheduled / default writes) |
Levels 2–15 follow site conventions. When priority is omitted the request carries no priority field and the device writes at level 16 (default); passing 8 writes level 8 explicitly. Example: write setpoint 21.0 to analog_value:5 —
{..., "value": "21.0", "priority": 8}→ level 8 = 21.0; if no higher level is occupied,present_valuebecomes 21.0;{..., "value": "21.0"}(omitted) → level 16 = 21.0; if someone previously wrote 19.0 at priority 8 and never released it,present_valuestays 19.0 — the write command succeeds but the present value doesn't move, the most classic BACnet pitfall.
REST example (switch a fan; binary objects take "true" / "false"):
curl -X POST -H "X-API-Key: $NEOMIND_API_KEY" \
-H "Content-Type: application/json" \
-d '{"command":"write_property","args":{"device_id":100,"object_type":"binary_output","instance":1,"value":"true","priority":8}}' \
http://localhost:9375/api/extensions/bacnet-bridge/command
8. Downstream Usage
Metrics from all three bridges are consumed identically.
Unified DataSourceId: every metric enters the platform as device:<device-id>:<metric-name>; dashboards, rules, and AI Chat all reference this format:
| Bridge | Device ID | Metric | DataSourceId |
|---|---|---|---|
| modbus-bridge | power_meter_1 | voltage | device:power_meter_1:voltage |
| opcua-bridge | opcua-ns_2_s_Temperature | value | device:opcua-ns_2_s_Temperature:value |
| bacnet-bridge | bacnet_100 | analog_input_1 | device:bacnet_100:analog_input_1 |
- Dashboard: bind the DataSourceIds above to metric cards / line charts to monitor voltage, temperature, energy, HVAC status, etc.
- Automation rules: set thresholds on any DataSourceId to trigger alerts or control writes (Automation Rules). Example "power-meter voltage over-limit alert" rule JSON:
{
"name": "Power meter voltage over-limit alert",
"trigger": { "trigger_type": "data_change" },
"condition": {
"condition_type": "comparison",
"source": "device:power_meter_1:voltage",
"operator": "greater_than",
"threshold": 250
},
"actions": [
{ "type": "notify", "message": "Power meter 1 voltage {value}V exceeds 250V", "severity": "critical" }
]
}
- AI Chat: natural-language queries like "voltage trend of meter 1 over the last 24h" or "what's the current status of AC unit 3".
8.1 End-to-End Mini Scenario: From the Meter to an Alert Notification
Wire the 5.3 power meter all the way to a notification; every value has a traceable origin:
- Connect: per 5.2,
add_deviceaddspower_meter_1withvoltage= holding 0–1,float32,scale: 0.1. - Confirm collection: after the first polling cycle,
get_device_datashowsvoltage = 220.15(raw[17673, 38912]=0x4509 0x9800→ 2201.5 × 0.1); the platform now has thedevice:power_meter_1:voltagemetric, gaining one data point every second. - Create the rule: on the automation-rules page create the rule JSON above. How each field maps to data:
trigger.trigger_type: data_change— every newvoltagereport (every second) triggers one condition evaluation;condition.source: device:power_meter_1:voltage— the DataSourceId assembled from device IDpower_meter_1(thedevice_idin add_device) + metric namevoltage(thenamein the register map);condition.operator / threshold— compare the metric's latest value against 250 (the business safety limit in this example);- the
{value}placeholder inactions[0].messageis replaced with the actual value at trigger time.
- Trigger: voltage spikes to 253.4 V → 253.4 > 250 matches → a notification with
severity: criticalis raised, the message renders as "Power meter 1 voltage 253.4V exceeds 250V", lands in the notification center, and can be forwarded through data-push channels (e.g. webhook); once voltage falls back below 250 nothing fires, and the metric curve and notification history remain queryable in the platform.
📷 TODO screenshot | Industrial-metrics dashboard · suggested path
…/neomind/industrial-protocols/04-dashboard.png
9. Troubleshooting
Start with three tools: the extension detail page's Logs tab for process output, the Metrics tab for error counters, and the relevant commands (list_devices / get_status) for device state. Common failures:
| Symptom | Likely cause | Solution |
|---|---|---|
Modbus device connected: false, total_poll_errors keeps growing | IP / port unreachable; wrong slave_id (1–247); timeout_ms too small; RTU serial path or baud rate mismatched | First verify connectivity from the host with ping / telnet ip port; check the slave address; raise timeout_ms (default 3000); for RTU verify serial_port and baud_rate. The extension reconnects automatically — connected returns to true once the link recovers |
float32 / uint32 values read via read_registers look wrong | Two-register type has count < 2, or word_order doesn't match the device | Set count to 2 for uint32 / int32 / float32; if the PLC is low-word-first set word_order to little (default big) |
read_registers returns arrays like [17673, 38912] instead of engineering values like 220.15 | read_registers returns raw 16-bit register words by protocol design; decoding and scaling only happen in the polling cycle | For engineering values use the value from get_device_data or the device metrics; keep data / raw for cross-checking against the register manual |
OPC-UA connect fails or drops repeatedly (security-mode rejection, expired session) | security_mode mismatched with the server's security policy; sign / sign_and_encrypt missing certificate or credentials; sessionTimeout too short | Match security_mode (none / sign / sign_and_encrypt) to the server policy; provide correct credentials or certificates; raise sessionTimeout (default 30000 ms); keep autoReconnect = true |
OPC-UA write returns an error and the value is not written | In the current 2.7.x open-source build write is a protective refusal (prevents accidental writes to industrial servers) | Expected behavior; perform writes from the device's own HMI / SCADA. Reads and subscriptions are unaffected |
| No data after OPC-UA subscribe | interval_ms outside 50–60000; the node value simply isn't changing; subscription never established | Check subscriptions_count and list_subscriptions; bring interval_ms back into range; use read first to confirm the node is readable |
BACnet discover returns nothing | Firewall blocks UDP 47808; broadcast unreachable across segments; wrong bindAddress | Allow UDP 47808 in both directions (including broadcast); keep NeoMind and the devices on the same Layer-2 network (broadcast doesn't route); leave bindAddress at 0.0.0.0; capture packets to confirm Who-Is goes out and I-Am comes back |
BACnet read_property / write_property fails with Device not found: … | The target device instance is not in the internal device table (never discovered or added) | Run discover first (or add_device with a known IP), then read/write |
BACnet write_property succeeds but present_value doesn't change | The written priority level is outranked by an occupied higher-priority level (e.g. an old value at level 8 while this write defaulted to level 16) | Raise the write priority (lower number = higher priority; 8 is the recommended default); or release the stale value occupying the higher level |
No notifications after BACnet subscribe_cov | The point doesn't support COV or its value never changes; it was unsubscribed | Fall back to periodic polling via add_device for points without COV support; cancellation requires the subscriber_id returned by subscribe_cov — after re-subscribing, verify active_cov_subscriptions in get_status |