Industrial Protocol Integration (Modbus / OPC-UA / BACnet)

Three protocol-bridge extensions for industrial devices — Modbus, OPC-UA, BACnet — sharing one pattern: connect → collect → register as device → feed dashboards.


1. Solution Overview

Industrial devices speak many protocols; NeoMind uses three independent bridge extensions, each turning its protocol's points into NeoMind device metrics and hiding protocol differences.

ProtocolExtensionTypical devicesDiscoveryData model
Modbusmodbus-bridgePLCs, power meters, temp/humidity sensors, VFDsManual (IP/serial + register map)Registers (Holding/Input/Coils/Discrete)
OPC-UAopcua-bridgeSCADA, MES, industrial gateways, OPC-UA serversBrowse address space; nodes auto-registerNodes (NodeID, any type)
BACnetbacnet-bridgeHVAC, fire, access, building controllersWho-Is/I-Am broadcastObjects (analog/binary/multi-state)

Data Flow (identical across all three):


2. Bill of Materials (BOM)

ItemSpecPurposeRequired
NeoMind platformv0.9.0+Extension host
Protocol bridgemodbus-bridge / opcua-bridge / bacnet-bridge (per device)Protocol access
Industrial devicesModbus / OPC-UA / BACnet-capable PLCs, meters, servers, controllersData source
Network reachableNeoMind and devices on the same segment or routableCommunication

Additional network requirements: Modbus RTU devices connect through a serial port on the host running NeoMind; BACnet/IP discovery relies on UDP 47808 broadcast (see 7.1).


3. Install the Extensions

All three bridges are published on the official extension marketplace; the current version is 2.7.x (this guide uses 2.7.7). Install one or more as needed — they are independent of each other.

  1. Open the Extensions tab in the left navigation.
  2. Click the Extension Marketplace button (globe icon) in the toolbar.
  3. Search for the extension name — modbus-bridge, opcua-bridge, or bacnet-bridge.
  4. Click Install on the matching entry; NeoMind automatically picks the .nep package matching your platform / ABI, downloads, and installs it.
  5. After installation the extension appears in the extension list and starts automatically.

3.2 CLI Install (Optional)

neomind extension market-list                        # Browse marketplace extensions
neomind extension market-install modbus-bridge # Install from marketplace (latest by default)
neomind extension market-install opcua-bridge --version 2.7.7
neomind extension market-install bacnet-bridge

3.3 Verify the Installation

  • The extension card and the header of the extension detail page should show Running (green dot).
  • Click the extension card to open the extension detail page and confirm the Overview / Config / Commands / Metrics / Logs tabs exist.
  • Switch to the Metrics tab and confirm extension-level metrics are being reported (e.g. connected_devices, total_poll_errors).

How to invoke commands: every operation of the three bridges (adding devices, browsing, read/write, subscribing) is an extension command. Two ways to invoke — fill in parameters on the Commands tab of the extension detail page; or call the REST API POST /api/extensions/:id/command with body {"command":"...","args":{...}}. The neomind extension CLI has no command-invocation subcommand. The examples below work with both.


4. Which Protocol to Choose

Your deviceChoose
Power/water meter, temp/humidity, VFD, small PLCModbus (most common, lightest)
SCADA / MES / industrial gateway / device exposing an OPC-UA serverOPC-UA (secure, self-describing, browsable)
HVAC, fresh air, fire, access, building controllerBACnet (building-automation standard)

If a device supports several, prefer OPC-UA (security + self-description + browsing).


5. Modbus (modbus-bridge)

The protocol and how the bridge works: Modbus is the most widely used master/slave protocol in industry — the master (NeoMind) reads and writes the device's raw 16-bit registers by slave address (slave_id): holding registers holding (FC03 read / FC06, FC16 write), input registers input (FC04), coils coil (FC01 read / FC05, FC15 write), and discrete inputs discrete_input (FC02). Registers carry no unit and no decimal point; real-world quantities (voltage, temperature, energy) come from decoding via type / scale / word_order in the register map (see section 5.4).

modbus-bridge works on a polling model: after add_device, each device gets its own polling thread that reads every point in the register map at the poll_interval_ms cadence, decodes it, and writes it to that device's metrics; the connection is kept alive, with automatic reconnect and a growing poll_errors counter on failure. This is periodic master-side sampling — data freshness depends on the polling interval, devices never push on their own.

Supports Modbus TCP and RTU (serial), multi-device independent polling, and register decoding (int16 / uint32 / float32 etc.) with scaling. Added devices are automatically registered as NeoMind devices (type modbus_device), and register values are continuously written as device metrics.

5.1 Extension-Level Configuration

View / edit on the Config tab of the extension detail page:

ParameterTypeDefaultRangeDescription
defaultPollIntervalInteger5000100–60000Default polling interval (ms) when not overridden per device
defaultTimeoutInteger3000100–30000Default connection timeout (ms)

5.2 Add a Device + Register Map

  1. Open the modbus-bridge extension detail page → Commands tab → select add_device.
  2. Fill the device parameter with the device configuration JSON (one command adds one device). Register addresses are 0-based: holding register 40001 in the PLC manual corresponds to address: 0:
{
"device_id": "power_meter_1",
"name": "Power Meter 1",
"mode": "tcp",
"ip": "192.168.1.50",
"port": 502,
"slave_id": 1,
"poll_interval_ms": 1000,
"timeout_ms": 3000,
"registers": [
{ "name": "voltage", "address": 0, "count": 2, "type": "float32", "register_type": "holding", "scale": 0.1, "unit": "V" },
{ "name": "energy", "address": 10, "count": 2, "type": "uint32", "register_type": "holding", "unit": "kWh" }
]
}
  1. On success the command returns:
{ "success": true, "device_id": "power_meter_1", "message": "Device added and polling started" }

The extension immediately starts the first polling cycle and registers the device with the platform (device type modbus_device). Running add_device again with the same device_id replaces the old configuration and restarts polling — no duplicate device is created. 4. RTU devices: set mode to "rtu", drop ip / port, and provide serial_port (e.g. /dev/ttyUSB0) and baud_rate (default 9600); slave_id and baud rate must match the device.

Device configuration fields (device JSON):

FieldTypeRequiredDefaultDescription
device_idstringDevice identifier; also used as the platform device ID
namestringoptionaldevice_idDisplay name
modestringtcp / rtu
ipstringrequired for TCPDevice IP address
portintegeroptional502Modbus TCP port
serial_portstringrequired for RTUSerial path (e.g. /dev/ttyUSB0)
baud_rateintegeroptional9600RTU baud rate
slave_idintegerSlave/unit ID (1–247)
poll_interval_msintegeroptional5000Polling interval (ms)
timeout_msintegeroptional3000Connection timeout (ms)
registersarrayoptionalRegister map (table below)

Register fields (each item of registers[]):

FieldTypeRequiredDefaultDescription
namestringRegister name; becomes the device metric name
addressinteger0-based start address
countintegeroptional1Number of registers to read; uint32 / int32 / float32 span 2 registers, so use 2
typestringDecode type: uint16 / int16 / uint32 / int32 / float32 / bool
register_typestringoptionalholdingholding (FC03) / input (FC04) / coil (FC01) / discrete_input (FC02)
scalenumberoptional0Raw value × scale (0 = no scaling), e.g. raw 245 × 0.1 → 24.5 °C
unitstringoptionalUnit
word_orderstringoptionalbigWord order for two-register types: big (hi word first, Modbus standard) / little (some PLCs)

Protocol limits: a single read fetches at most 125 registers for holding / input and 2000 for coil / discrete_input. Entries exceeding the limit are skipped and logged.

📷 TODO screenshot | add_device config · suggested path …/neomind/industrial-protocols/01-modbus-add.png

5.3 Verification (End to End: From Adding to Metrics)

After adding power_meter_1 per 5.2, a complete verification timeline:

  1. After the first polling cycle (about 1 second with poll_interval_ms: 1000): the Devices page shows power_meter_1 (Modbus Device) carrying connected / poll_errors / last_poll_ms plus one metric per register (voltage, energy).
  2. Run get_device_data (arg {"device_id": "power_meter_1"}) to check the decoded values:
{
"success": true,
"device_id": "power_meter_1",
"connected": true,
"poll_errors": 0,
"last_poll_ms": 12,
"registers": [
{ "name": "voltage", "value": 220.15, "unit": "V", "raw": [17673, 38912] },
{ "name": "energy", "value": 100000.0, "unit": "kWh", "raw": [1, 34464] }
]
}

Where the values come from: for voltage the wire carried two words 0x4509 and 0x9800 → decoded as float32 = 2201.5 → × scale: 0.1 = 220.15 V; for energy the wire carried 0x0001 and 0x86A0 → joined as uint32 = 100000 (no scale set, no scaling) → 100000 kWh. The raw array holds the raw 16-bit register words (shown in decimal) — compare them word by word against the device's register manual when debugging decoding.

  1. Run list_devices to check device and polling health:
{
"success": true,
"count": 1,
"devices": [
{ "device_id": "power_meter_1", "name": "Power Meter 1", "mode": "tcp", "connected": true,
"register_count": 2, "poll_interval_ms": 1000, "poll_errors": 0, "last_poll_ms": 12 }
]
}
  1. Extension detail page Metrics tab: connected_devices ≥ 1 and total_poll_errors no longer growing.
  2. Metrics enter the platform with DataSourceIds like device:power_meter_1:voltage and device:power_meter_1:energy, ready to bind to dashboards or rules.

5.4 Decoding: Register Words → Engineering Values

The wire only ever carries unsigned 16-bit words; type decides how 1–2 words are interpreted, word_order decides the join order for two-register types, and scale applies one multiplication after decoding:

  1. Single-register types (count: 1): uint16 is used as-is; int16 is interpreted as two's complement (e.g. wire value 0xFF9C = 65436 → interpreted as −100; with scale: 0.1 that is −10.0 °C, a cold-storage scenario); bool maps any non-zero word to 1.

  2. Two-register types (uint32 / int32 / float32, count must be 2): the two words are joined into 32 bits and then interpreted. Take the voltage register from 5.3, words 0x4509 and 0x9800:

    • word_order: big (default, Modbus standard, hi word first): (0x4509 << 16) | 0x9800 = 0x45099800 → IEEE 754 float 2201.5 → × scale 0.1220.15 V;
    • word_order: little (some PLCs put the lo word first): (0x9800 << 16) | 0x4509 = 0x98004509 → decodes to garbage like −1.66×10⁻²⁴.
    • The uint32 energy works the same way: 0x0001, 0x86A0 → big join 0x000186A0 = 100000 kWh; if the device is actually little and you read it as big, you get 0x86A00001 ≈ 2.55×10⁹ — an astronomically wrong number.

    When readings look absurd (huge or tiny negative), suspect word_order and count first.

  3. scale: decoded value × scale; scale: 0 (default) means no scaling. Common conversions: temperature raw 245 × 0.1 → 24.5 °C; voltage raw 2301 × 0.001 → 2.301 V. The multiplication happens after type decoding — float32 values can be scaled too.

5.5 Read / Write Control

  • Read: read_registers(device_id, address, count) (on-demand read; register_type accepts holding (default) / input, max 125 registers per call).
  • Write: write_register(device_id, address, value), write_registers(...values[]), write_coil(device_id, address, value), write_coils(...values[]) — e.g. remote breaker close or setpoint changes.
  • Operations: update_polling to change the poll interval, set_register_map to update the register map (polling restarts after replacement), remove_device to remove a device and unregister it from the platform.

Read holding registers — call arguments:

{ "device_id": "power_meter_1", "address": 0, "count": 2 }

Return:

{ "success": true, "device_id": "power_meter_1", "address": 0, "register_type": "holding", "count": 2, "data": [17673, 38912] }
data is raw words

The data returned by read_registers consists of raw 16-bit words with no type decoding or scaling (decoding only happens in the polling cycle). For engineering values use the value from get_device_data or the device metrics; keep data for cross-checking against the register manual.

Write a single holding register — call arguments:

{ "device_id": "power_meter_1", "address": 100, "value": 250 }

Return:

{ "success": true, "device_id": "power_meter_1", "address": 100, "value": 250, "message": "Register written successfully" }

Write limits: write_register value must be 0–65535; write_registers accepts at most 123 values per call; write_coil value takes the strings "true" / "false"; write_coils takes a boolean array, at most 1968 per call.

Fill in parameters on the Commands tab, or call the REST API to write a single holding register:

curl -X POST -H "X-API-Key: $NEOMIND_API_KEY" \
-H "Content-Type: application/json" \
-d '{"command":"write_register","args":{"device_id":"power_meter_1","address":100,"value":250}}' \
http://localhost:9375/api/extensions/modbus-bridge/command

6. OPC-UA (opcua-bridge)

The protocol and how the bridge works: OPC-UA is the information-interchange standard of industrial automation; its biggest difference from Modbus is that it is self-describing — the server organizes data into an address-space tree where every node has a NodeID, browse name, and data type, so clients can discover points by browsing like a filesystem instead of transcribing register maps by hand; and it adds signing / encryption plus username/password authentication at the transport layer.

opcua-bridge works on a subscription model: connect establishes a session → browse walks the address space (browsed nodes enter the local cache and auto-register as NeoMind devices) → subscribe creates data-change subscriptions for the nodes you care about. Once subscribed, any change in a node value (sampled at interval_ms) is landed on that node device's metrics — no need to poll every point, and no chat/notification-center messages are produced; updates appear as metrics on the Devices page and dashboards.

Connect to any OPC-UA server (opc.tcp://) with security mode none / sign / sign_and_encrypt and optional username/password, with automatic reconnect. Browsed nodes auto-register as NeoMind devices (type opcua_node) and continuously publish metrics — no per-point configuration needed.

6.1 Extension-Level Configuration

ParameterTypeDefaultRangeDescription
sessionTimeoutInteger300001000–300000OPC-UA session timeout (ms)
autoReconnectString"true"true / falseReconnect automatically on connection loss

6.2 Connect (and Choosing a Security Mode)

  1. Open the opcua-bridge extension detail page → Commands tab → run connect:
{ "server_url": "opc.tcp://192.168.1.60:4840", "security_mode": "sign_and_encrypt", "username": "op", "password": "***" }

After a successful connect, the server itself is registered as a device too (type opcua_server; ID is derived from the sanitized URL — : / . replaced with _, e.g. opcua-server-opc_tcp___192_168_1_60_4840) and carries the connection-level metrics; on disconnect it reconnects automatically per autoReconnect.

  1. How to pick the security mode (it must match the server-side policy exactly, otherwise the server rejects the session):
security_modeMessage protectionWhen to usePrerequisites
none (default)Plaintext, unsignedIsolated / controlled test segments, demosNone
signSigned (tamper-proof), still plaintextTrusted intranets needing integrity onlyClient certificate trusted by the server
sign_and_encryptSigned + encryptedProduction, cross-segment transportServer-trusted client certificate + credentials

Certificates and credentials follow the server's security policy: for sign / sign_and_encrypt request a client certificate from the OPC-UA server administrator and have it trusted; username / password are accounts created in the server's user management. Prefer sign_and_encrypt whenever possible; only fall back to none when the server exclusively offers a None policy (a common vendor debug default — consider enabling a security policy on the server after evaluation).

6.3 Browse the Address Space and Auto-Registration

Run browse: node_id defaults to the root i=84 (the Objects folder is i=85 — recommended starting point for business points); max_depth defaults to 1 level, up to 10. The return JSON looks like:

{
"success": true,
"browse_from": "i=85",
"max_depth": 1,
"nodes": [
{ "node_id": "ns=2;s=Temperature", "browse_name": "Temperature", "display_name": "Temperature Sensor", "node_class": "Variable", "data_type": "Float" },
{ "node_id": "ns=2;s=Pressure", "browse_name": "Pressure", "display_name": "Pressure Sensor", "node_class": "Variable", "data_type": "Float" }
]
}
  • Every node carries node_id / browse_name / display_name / node_class (Object / Variable etc.); variable nodes also carry data_type.
  • Browsed nodes are simultaneously placed into the local node cache (queryable via list_nodes / get_node) and auto-registered as NeoMind devices — this is where "no per-point configuration" comes from. Naming rule: =, ;, : and spaces in the node ID are replaced with _, prefixed with opcua-:
Node NodeIDGenerated device IDMetric DataSourceId
i=2258opcua-i_2258device:opcua-i_2258:value
ns=2;s=Temperatureopcua-ns_2_s_Temperaturedevice:opcua-ns_2_s_Temperature:value

Node IDs use standard OPC-UA notation: i=2258 (numeric) or ns=2;s=Temperature (namespaced string).

📷 TODO screenshot | browse address space · suggested path …/neomind/industrial-protocols/02-opcua-browse.png

6.4 Subscribe to Data Changes

Run subscribe: node_ids accepts a JSON array or a comma-separated string; interval_ms defaults to 1000 (range 50–60000).

{ "node_ids": ["ns=2;s=Temperature", "ns=2;s=Pressure"], "interval_ms": 500 }

Return:

{ "success": true, "subscription_id": "sub-9f3c1a2e-…", "node_ids": ["ns=2;s=Temperature", "ns=2;s=Pressure"], "interval_ms": 500 }

Re-running subscribe for the same set of nodes does not create a duplicate — it returns "Subscription already exists for these nodes".

What a subscription push looks like — metric updates, not messages: when a node value changes, the bridge stores the new value together with quality (e.g. Good) and source_timestamp (server source timestamp) into the node cache, and once per metric cycle writes the three values to the node device (device_metrics_write):

{ "device_id": "opcua-ns_2_s_Temperature", "metric": "value", "value": 43.0, "timestamp": 1760000000000 }

In other words, what you see on the Devices page / dashboards is a new data point on the device:opcua-ns_2_s_Temperature:value metric; automation rules trigger on it as usual. No "OPC-UA message" ever reaches the notification center.

6.5 Verification

  • Run get_status:
{ "success": true, "connected": true, "nodes_count": 12, "subscriptions_count": 2, "total_commands": 9 }
  • Extension detail page Metrics tab: connected = 1, nodes_count grows as you browse, subscriptions_count equals the number of active subscriptions.
  • The Devices page shows opcua-<node-id> devices; each node device carries three metrics: value / quality / source_timestamp.
  • Metrics enter the platform with a DataSourceId like device:opcua-ns_2_s_Temperature:value.
  • The read command (arg node_ids) returns current node values so you can immediately verify collection.

6.6 Read / Write Control

Bulk-read current valuesread(node_ids) returns:

{
"success": true,
"results": [
{ "node_id": "ns=2;s=Temperature", "value": 42.5, "quality": "Good" },
{ "node_id": "ns=2;s=Pressure", "value": 101.3, "quality": "Good" }
]
}

read returns the latest value held in the node cache (updated by browse / subscribe) — prefer subscriptions to keep data fresh.

Write a node value: write(node_id, value, data_type)value is a string; data_type is optional (e.g. Float, Int32) to specify the type explicitly.

write is a protective stub

In the current open-source build (2.7.x), write is a protective stub: the command returns an error and does not write to the server — preventing accidental writes to industrial servers from the bridge layer. For write control on OPC-UA points, use the device's own HMI / SCADA. Reads and subscriptions are unaffected.

  • Unsubscribe / disconnect: unsubscribe(node_ids) (node_ids format same as subscribe), disconnect (clears the node cache and subscriptions).
  • Helper commands: list_nodes / get_node(node_id) show cached node details (including value / quality / source_timestamp); list_subscriptions lists all active subscriptions (subscription_id / node_ids / interval_ms / active).

REST example (read two nodes):

curl -X POST -H "X-API-Key: $NEOMIND_API_KEY" \
-H "Content-Type: application/json" \
-d '{"command":"read","args":{"node_ids":["i=2258","ns=2;s=Temperature"]}}' \
http://localhost:9375/api/extensions/opcua-bridge/command

7. BACnet (bacnet-bridge)

The protocol and how the bridge works: BACnet is the building-automation standard protocol (HVAC, fresh air, lighting, fire, access control). Its data model is objects: each device is identified by a device instance number (0–4194303) and carries a set of objects (e.g. analog_input:1, binary_output:1), each with properties — the most used being present_value (property 85). Control writes never touch the present value directly; they write into the object's internal 16-level priority array (lower number = higher priority, see 7.4).

bacnet-bridge runs two kinds of background tasks on UDP 47808: one listener thread that receives I-Am responses and COV notifications, plus one polling thread per added device that periodically reads point present values. Polling is enough for slow-changing points; COV subscription is the choice for second-level responsiveness — the device pushes on every change, more real-time and lighter than polling.

BACnet/IP over UDP (default 47808) with Who-Is/I-Am discovery, property reads, control writes, and COV subscriptions. Discovered / added devices auto-register as NeoMind devices (type bacnet_device, ID bacnet_<device_id>).

7.1 Extension-Level Configuration

ParameterTypeDefaultRangeDescription
bindAddressString0.0.0.0Local IP to bind for BACnet/IP
bindPortInteger478081–65535UDP port for BACnet/IP
defaultTimeoutMsInteger3000100–30000Default request timeout (ms)
pollIntervalMsInteger100001000–60000Default polling interval (ms)

Deployment requirement: Who-Is/I-Am uses UDP broadcast. The network must allow sending/receiving UDP 47808 (including broadcast); broadcast does not cross routers, so NeoMind and the BACnet devices should be on the same Layer-2 network, or interconnected via a network that forwards broadcast.

7.2 Discover Devices + Add Polled Points

  1. Open the bacnet-bridge extension detail page → Commands tab → run discover (optionally low_id / high_id to bound the device-instance range, default 0–4194303; timeout_ms defaults to 3000 as the wait window). The extension sends a Who-Is broadcast to 255.255.255.255:47808 and collects I-Am responses during the window (up to 500 devices). The return JSON:
{
"success": true,
"count": 2,
"devices": [
{ "device_id": 100, "ip": "192.168.1.100", "port": 47808, "vendor_id": 5, "max_apdu": 1476 },
{ "device_id": 201, "ip": "192.168.1.101", "port": 47808, "vendor_id": 15, "max_apdu": 480 }
]
}

Field meanings: device_id is the BACnet device instance number (configured on the device, unique network-wide); vendor_id is the ASHRAE-assigned vendor number (numeric — useful for identifying the brand); max_apdu is the device's maximum APDU size. Note: discovery is not registration — discovered devices enter the internal device table (visible in list_devices, connected: true), but only devices added via add_device are registered into the NeoMind platform and produce metrics.

  1. Run list_devices to see discovered devices, and get_device / list_objects to inspect a device's objects (analog / binary / multi-state input / output / value; each item carries object_type / instance / present_value / units / cov_subscribed).
  2. Run add_device to register a device manually and start polling selected points (device parameter):
{
"device_id": 100,
"ip": "192.168.1.100",
"port": 47808,
"name": "HVAC Controller",
"poll_interval_ms": 5000,
"objects": [
{ "object_type": "analog_input", "instance": 1, "name": "Temperature", "units": "degC" },
{ "object_type": "analog_input", "instance": 2, "name": "Humidity", "units": "%" },
{ "object_type": "binary_output", "instance": 1, "name": "Fan Status" }
]
}

It returns {"success": true, "device_id": 100, "ip": "192.168.1.100", "port": 47808, "message": "Device added and polling started"} — the device is registered into the platform as bacnet_100, and the polling thread reads each object's present_value into metrics every poll_interval_ms.

📷 TODO screenshot | Who-Is discovery · suggested path …/neomind/industrial-protocols/03-bacnet-discover.png

7.3 Verification

  • Run get_status for a global view:
{
"success": true,
"status": {
"total_devices": 1, "connected_devices": 1,
"total_cov_subscriptions": 0, "active_cov_subscriptions": 0,
"listener_running": true, "bind_port": 47808
}
}
  • Extension detail page Metrics tab: connected_devices ≥ 1; after COV subscriptions, cov_subscriptions grows.
  • The Devices page shows bacnet_100 (BACnet Device). Each polled object's present value becomes a device metric named <object_type>_<instance> (e.g. analog_input_1, binary_output_1), alongside connected / objects_count / last_seen.
  • Metrics enter the platform with a DataSourceId like device:bacnet_100:analog_input_1.
  • The list_objects command lets you confirm that present values refresh and cov_subscribed gets set.

7.4 Read Properties / Subscribe COV / Write Control

Prerequisite: the target device instance must already be in the internal device table (run discover or add_device first), otherwise the command fails with Device not found: ….

Read a propertyread_property call arguments (object_type defaults to analog_input; property_id defaults to 85; common values: 85 = present_value, 77 = object_name, 28 = description, 117 = units):

{ "device_id": 100, "object_type": "analog_input", "instance": 1, "property_id": 85 }

Return:

{ "success": true, "device_id": 100, "object_type": "analog_input", "instance": 1, "property_id": 85, "value": 23.5 }

The value type follows the property: present values are numeric (true / false for binary objects, a state number for multi-state), while text properties like object_name (77) return strings. If the device refuses the read you get BACnet error: class=…, code=…. To read several properties in one request use read_property_multiple (properties defaults to [85]):

{ "device_id": 100, "objects": [
{ "object_type": "analog_input", "instance": 1, "properties": [85, 77] },
{ "object_type": "analog_input", "instance": 2 }
] }

Return:

{ "success": true, "device_id": 100, "count": 3, "values": [
{ "object_type": "analog_input", "instance": 1, "property_id": 85, "value": 23.5 },
{ "object_type": "analog_input", "instance": 1, "property_id": 77, "value": "Room Temp" },
{ "object_type": "analog_input", "instance": 2, "property_id": 85, "value": 41.2 }
] }

Subscribe to COVsubscribe_cov(device_id, object_type, instance), lifetime defaults to 0 (indefinite, in seconds), confirmed defaults to true (device must acknowledge each notification):

{ "device_id": 100, "object_type": "analog_input", "instance": 1 }

Return:

{ "success": true, "subscriber_id": 1, "device_id": 100, "object_type": "analog_input", "instance": 1, "lifetime": 0, "confirmed": true, "message": "COV subscription active" }

What you receive after a COV subscription — again metric updates, not messages: when the point changes, the device pushes a COV notification (subscriber ID + object identifier + list of property values); the bridge's background listener parses it, updates the point's present_value in the internal object cache, and sets cov_subscribed = true; the value then flows to the platform as the device:bacnet_100:analog_input_1 metric — you see the present value refresh on the Devices page / dashboards and rules trigger as usual. list_objects shows the object's refreshed present_value and cov_subscribed: true, and get_status counts it in active_cov_subscriptions. To cancel, call unsubscribe_cov with the subscriber_id returned by subscribe_cov.

Write controlwrite_property(device_id, object_type, instance, value, priority). Only output / value objects are writable (analog_output, binary_value, etc.; inputs are read-only). Always pass value as a string; the bridge infers the type in order: "true" / "false" → boolean (use for binary objects); pure integer → unsigned integer; decimal → real; anything else → string. Integer writes to analog output / value are coerced to REAL per ASHRAE 135-2020.

priority and priority-array semantics: a write does not set present_value directly — it writes one level of the object's 16-level priority array (1 highest, 16 lowest), and present_value always equals the highest-priority non-empty level. Common level conventions:

LevelConventional use
1Life safety (highest — do not use)
8Manual operator / maintenance writes (used in this extension's examples)
16Lowest (BACnet default level — scheduled / default writes)

Levels 2–15 follow site conventions. When priority is omitted the request carries no priority field and the device writes at level 16 (default); passing 8 writes level 8 explicitly. Example: write setpoint 21.0 to analog_value:5

  • {..., "value": "21.0", "priority": 8} → level 8 = 21.0; if no higher level is occupied, present_value becomes 21.0;
  • {..., "value": "21.0"} (omitted) → level 16 = 21.0; if someone previously wrote 19.0 at priority 8 and never released it, present_value stays 19.0 — the write command succeeds but the present value doesn't move, the most classic BACnet pitfall.

REST example (switch a fan; binary objects take "true" / "false"):

curl -X POST -H "X-API-Key: $NEOMIND_API_KEY" \
-H "Content-Type: application/json" \
-d '{"command":"write_property","args":{"device_id":100,"object_type":"binary_output","instance":1,"value":"true","priority":8}}' \
http://localhost:9375/api/extensions/bacnet-bridge/command

8. Downstream Usage

Metrics from all three bridges are consumed identically.

Unified DataSourceId: every metric enters the platform as device:<device-id>:<metric-name>; dashboards, rules, and AI Chat all reference this format:

BridgeDevice IDMetricDataSourceId
modbus-bridgepower_meter_1voltagedevice:power_meter_1:voltage
opcua-bridgeopcua-ns_2_s_Temperaturevaluedevice:opcua-ns_2_s_Temperature:value
bacnet-bridgebacnet_100analog_input_1device:bacnet_100:analog_input_1
  • Dashboard: bind the DataSourceIds above to metric cards / line charts to monitor voltage, temperature, energy, HVAC status, etc.
  • Automation rules: set thresholds on any DataSourceId to trigger alerts or control writes (Automation Rules). Example "power-meter voltage over-limit alert" rule JSON:
{
"name": "Power meter voltage over-limit alert",
"trigger": { "trigger_type": "data_change" },
"condition": {
"condition_type": "comparison",
"source": "device:power_meter_1:voltage",
"operator": "greater_than",
"threshold": 250
},
"actions": [
{ "type": "notify", "message": "Power meter 1 voltage {value}V exceeds 250V", "severity": "critical" }
]
}
  • AI Chat: natural-language queries like "voltage trend of meter 1 over the last 24h" or "what's the current status of AC unit 3".

8.1 End-to-End Mini Scenario: From the Meter to an Alert Notification

Wire the 5.3 power meter all the way to a notification; every value has a traceable origin:

  1. Connect: per 5.2, add_device adds power_meter_1 with voltage = holding 0–1, float32, scale: 0.1.
  2. Confirm collection: after the first polling cycle, get_device_data shows voltage = 220.15 (raw [17673, 38912] = 0x4509 0x9800 → 2201.5 × 0.1); the platform now has the device:power_meter_1:voltage metric, gaining one data point every second.
  3. Create the rule: on the automation-rules page create the rule JSON above. How each field maps to data:
    • trigger.trigger_type: data_change — every new voltage report (every second) triggers one condition evaluation;
    • condition.source: device:power_meter_1:voltage — the DataSourceId assembled from device ID power_meter_1 (the device_id in add_device) + metric name voltage (the name in the register map);
    • condition.operator / threshold — compare the metric's latest value against 250 (the business safety limit in this example);
    • the {value} placeholder in actions[0].message is replaced with the actual value at trigger time.
  4. Trigger: voltage spikes to 253.4 V → 253.4 > 250 matches → a notification with severity: critical is raised, the message renders as "Power meter 1 voltage 253.4V exceeds 250V", lands in the notification center, and can be forwarded through data-push channels (e.g. webhook); once voltage falls back below 250 nothing fires, and the metric curve and notification history remain queryable in the platform.

📷 TODO screenshot | Industrial-metrics dashboard · suggested path …/neomind/industrial-protocols/04-dashboard.png


9. Troubleshooting

Start with three tools: the extension detail page's Logs tab for process output, the Metrics tab for error counters, and the relevant commands (list_devices / get_status) for device state. Common failures:

SymptomLikely causeSolution
Modbus device connected: false, total_poll_errors keeps growingIP / port unreachable; wrong slave_id (1–247); timeout_ms too small; RTU serial path or baud rate mismatchedFirst verify connectivity from the host with ping / telnet ip port; check the slave address; raise timeout_ms (default 3000); for RTU verify serial_port and baud_rate. The extension reconnects automatically — connected returns to true once the link recovers
float32 / uint32 values read via read_registers look wrongTwo-register type has count < 2, or word_order doesn't match the deviceSet count to 2 for uint32 / int32 / float32; if the PLC is low-word-first set word_order to little (default big)
read_registers returns arrays like [17673, 38912] instead of engineering values like 220.15read_registers returns raw 16-bit register words by protocol design; decoding and scaling only happen in the polling cycleFor engineering values use the value from get_device_data or the device metrics; keep data / raw for cross-checking against the register manual
OPC-UA connect fails or drops repeatedly (security-mode rejection, expired session)security_mode mismatched with the server's security policy; sign / sign_and_encrypt missing certificate or credentials; sessionTimeout too shortMatch security_mode (none / sign / sign_and_encrypt) to the server policy; provide correct credentials or certificates; raise sessionTimeout (default 30000 ms); keep autoReconnect = true
OPC-UA write returns an error and the value is not writtenIn the current 2.7.x open-source build write is a protective refusal (prevents accidental writes to industrial servers)Expected behavior; perform writes from the device's own HMI / SCADA. Reads and subscriptions are unaffected
No data after OPC-UA subscribeinterval_ms outside 50–60000; the node value simply isn't changing; subscription never establishedCheck subscriptions_count and list_subscriptions; bring interval_ms back into range; use read first to confirm the node is readable
BACnet discover returns nothingFirewall blocks UDP 47808; broadcast unreachable across segments; wrong bindAddressAllow UDP 47808 in both directions (including broadcast); keep NeoMind and the devices on the same Layer-2 network (broadcast doesn't route); leave bindAddress at 0.0.0.0; capture packets to confirm Who-Is goes out and I-Am comes back
BACnet read_property / write_property fails with Device not found: …The target device instance is not in the internal device table (never discovered or added)Run discover first (or add_device with a known IP), then read/write
BACnet write_property succeeds but present_value doesn't changeThe written priority level is outranked by an occupied higher-priority level (e.g. an old value at level 8 while this write defaulted to level 16)Raise the write priority (lower number = higher priority; 8 is the recommended default); or release the stale value occupying the higher level
No notifications after BACnet subscribe_covThe point doesn't support COV or its value never changes; it was unsubscribedFall back to periodic polling via add_device for points without COV support; cancellation requires the subscriber_id returned by subscribe_cov — after re-subscribing, verify active_cov_subscriptions in get_status

10. Appendix